3 contributions to Functional Safety Play Book
NEW: Incident Autopsy Live 🔍
Starting next Friday, we'll review a US Chemical Safety Board incident reconstruction together and look at it from a functional safety point of view. For each incident we'll work through: ➡️ What the hazard was and what should have prevented it ➡️ Where the SIS, alarms or other safeguards failed ➡️ Where in the safety lifecycle the failure started ➡️ Whether it could happen on your project After each session I'll post a short summary of the lessons from experience, so we build up a library over time. First session: 📅 Friday 2nd October ⏰ 10:00 UK 📍 Link in the calendar Comment below if you're wanting to attend. I’ll put a link to the case beforehand
0 likes • 27d
Hi Ricard, Thanks for putting this together and for taking the time to run these sessions. One question for future sessions: would you be able to offer some sessions at a time that works better for US-based professionals, perhaps in the UK afternoon? I’d really like to attend when I can.
Valve SIL Calculation
Good morning Everyone, For valve SIL calculations, do we need to include the failure rates of all valve components, such as the solenoid, actuator, and valve body? Should the actuator and valve body also be included?
0 likes • Sep 11
Dear Richard, thank you for explanation. Then how I am going to find Valve Assembly λDU? Which option should be proper, any standard I can refer? 1. Valve PFDavg = Body PFD + Actuator PFD + Solenoid PFD 2. Valve PFDavg = should be calculated 3oo3 method. (I do not remember formula for it). Application is fail safe, no air or power supply should be taken into account. Any fail state valve will go to fail position. Thank you!
SIL Calculation
Good day everyone, I have few questions on SIL Calculation. I have a PILZ controller in SIF and try to make some calculation by hand. Controller has DI and DO with CPU. 1. If I would like to calculate PFDavg for Controller then I should combine DI, DO and CPU PFD avarage, correct? (No redundancy at DIs and DOs) For ex, PFD input, single + PFD output, single+ PFD CPU = 2,20 x 10^-4 + 1,30 x 10^-5 + 6,20 x 10^-5 (See please certificate) 2. As you see the certificate shows only PFD but not λ DU. Can I calculate my λDU from PFD as referencing the formula below? PFDavg = (λDU * T)/2 . Actually, the certificate does not say what T has been taken into account on PFD calculation as well, but I am going to take it as 1 year. 3. CPU Part: 773103 ( PNOZ m1p ETH) ; Certificate Link: https://www.pilz.com/download/open/PNOZmulti_TUEV-Sued_BM_M6A-020132-0284-R01_R4_4_valid_2030-Jun-24_1002803-BM-34.pdf Thank you!
0 likes • Aug 25
@Dmitry Kosianchik Hello , thanks for sharing information on this topic. 1. You have to combine CPU PFD with Channels PFD while calculating overall SLS PFD. There are some example on the book Safety Instrumented Systems Verification: Practical Probabilistic Calculations. 2. I agree with you, that was weird certificate.
0 likes • Aug 25
@Tomasz Barnert thanks for detailed information. I calculated λDU for few components and you are right they are equal to PFH. Thank you for helping!